Condensation risk in a room with a high latent load and chilled ceiling panels and with air supplied from a liquid desiccant system.(Report): An article from: HVAC & R Research Buy on Amazon

https://www.ebooknetworking.net/books_detail-B0027YU0W0.html

Condensation risk in a room with a high latent load and chilled ceiling panels and with air supplied from a liquid desiccant system.(Report): An article from: HVAC & R Research

9.95 USD
Buy New on Amazon 🇺🇸

Available for download now

Book Details

ISBN / ASINB0027YU0W0
ISBN-13978B0027YU0W9
AvailabilityAvailable for download now
Sales Rank11,147,571
MarketplaceUnited States  🇺🇸

Description

This digital document is an article from HVAC & R Research, published by American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. on March 1, 2009. The length of the article is 4726 words. The page length shown above is based on a typical 300-word page. The article is delivered in HTML format and is available immediately after purchase. You can view it with any web browser.

From the author: Radiant cooling has shown great advantages when it comes to improving thermal comfort and can also reduce energy demand. But the system may have a high condensation risk if used with a high latent load. This study proposes a new type of ventilation system that uses a radiant cooling panel and air supplied from a liquid desiccant dehumidification system, which provides very dry supply air and chilled water for radiant cooling. This study uses an office with a high latent load to demonstrate the application of such a system in a hot and humid climate. By using a validated computational fluid dynamics (CFD) program to calculate the distributions of air temperature, humidity, and velocity, as well as the predicted mean vote in the office, the results show that the new system could reduce the risk of condensation on the cooling panels and offer a comfortable indoor environment. The new system has great potential when it comes to use in hot and humid climate regions.

Citation Details
Title: Condensation risk in a room with a high latent load and chilled ceiling panels and with air supplied from a liquid desiccant system.(Report)
Author: Yonggao Yin
Publication:HVAC & R Research (Magazine/Journal)
Date: March 1, 2009
Publisher: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
Volume: 15 Issue: 2 Page: 315(13)

Article Type: Report

Distributed by Gale, a part of Cengage Learning
Donate to EbookNetworking
Prev
Next