Dynamic model-based fault tolerant control of variable air volume air conditioning system.(Report): An article from: HVAC & R Research
Book Details
Author(s)Atanu Talukdar, Amit Patra
PublisherTaylor & Francis Ltd.
ISBN / ASINB003UKZ2N2
ISBN-13978B003UKZ2N7
MarketplaceIndia 🇮🇳
Description
This digital document is an article from HVAC & R Research, published by Taylor & Francis Ltd. on March 1, 2010. The length of the article is 7349 words. The page length shown above is based on a typical 300-word page. The article is delivered in HTML format and is available immediately after purchase. You can view it with any web browser.
From the author: A dynamic model-based fault tolerant control of a variable air volume air conditioning system is developed. State space model of the variable air volume air conditioning system is used to detect, isolate, and estimate stuck faults of the damper vanes of the air handling unit (AHU). Fault identification is implemented by an adaptive interactive multiple observer scheme. It has been shown analytically that observers representing faults in two mutually redundant variable air volume flow control boxes wrongly converge to the same value even when fault has occurred in only one variable air volume flow control box. An input modification scheme is proposed to prevent convergence of the observer corresponding to the functional variable air volume box. Using the information regarding the fault, its effect is minimized. This is achieved by applying the control distribution concept.
Citation Details
Title: Dynamic model-based fault tolerant control of variable air volume air conditioning system.(Report)
Author: Atanu Talukdar
Publication:HVAC & R Research (Magazine/Journal)
Date: March 1, 2010
Publisher: Taylor & Francis Ltd.
Volume: 16 Issue: 2 Page: 233(22)
Article Type: Report
Distributed by Gale, a part of Cengage Learning
From the author: A dynamic model-based fault tolerant control of a variable air volume air conditioning system is developed. State space model of the variable air volume air conditioning system is used to detect, isolate, and estimate stuck faults of the damper vanes of the air handling unit (AHU). Fault identification is implemented by an adaptive interactive multiple observer scheme. It has been shown analytically that observers representing faults in two mutually redundant variable air volume flow control boxes wrongly converge to the same value even when fault has occurred in only one variable air volume flow control box. An input modification scheme is proposed to prevent convergence of the observer corresponding to the functional variable air volume box. Using the information regarding the fault, its effect is minimized. This is achieved by applying the control distribution concept.
Citation Details
Title: Dynamic model-based fault tolerant control of variable air volume air conditioning system.(Report)
Author: Atanu Talukdar
Publication:HVAC & R Research (Magazine/Journal)
Date: March 1, 2010
Publisher: Taylor & Francis Ltd.
Volume: 16 Issue: 2 Page: 233(22)
Article Type: Report
Distributed by Gale, a part of Cengage Learning